Online UPS with integrated PIM and programmable display
| Voltage | 75 VAC to 155 VAC (before going to batteries) |
|---|---|
| Frequency | 45 Hz to 65 Hz |
| Voltage | 120 VAC ±3% |
|---|---|
| Frequency | 50 Hz or 60 Hz |
| Current | 10.4 A |
| Rating | 1250 VA / 875 W |
| Crest Factor Ratio | 50% load up to 4.8:1, 75% load up to 3.2:1, 100% load up to 2.4:1 |
| THD | 4.00% maximum |
| Dynamic Response | ±4% for 100% step load change 0.5 ms recovery time |
| Overload | 110% for 10 sec; 200% for 50 ms |
| UPS Protection | Input and output short circuit, Input and output overload, Excessive battery discharge |
| Temperature | -40°C to +74°C (-40°F to +165°F) |
|---|---|
| Humidity | 0% to 95% non-condensing |
| Altitude | Sea level to 10,000 ft |
| Input | Hardwired to bypass box |
|---|---|
| Outputs | Hardwired to bypass box, with single 15 Amp receptacle |
| Dimensions H x W x D (in) |
3.5 x 19.0 x 10.0 (2U) |
| Weight (lb) | 13 |
| Cooling | Low velocity, Forced air |
| Standard Features | Power factor corrected input, Fully regenerative, True on-line continuous power, Low distortion sine wave output, Designed for non-linear loads, Extended brownout protection, EIA/RS232 data interface |
|---|---|
| Certifications | IEEE 587/ANSI C62.4, IEC 555 @ 120 VA, NEMA |
| Typical Recharge Time (to 85% Capacity @ 100% Load) |
48-72 hrs (more time required with extended battery option) |
| Switches / Control Panel | System power, Cold start, Test, Alarm silence, Four line LCD display panel |
|---|---|
| Audible Alarms | Utility interrupt, Inverter failure, Overload, Low battery, Self test |
| Intelligent Computer Interfaces | Serial interface for EIA 232, 1 each DB9-F (RS232 and signal interface pins) and 1 each USB, Full interactive remote computer monitoring and control of most features including load control (requires optional monitoring software), NTCIP and TCP/IP ready |
| Contact Closures | "D" connector, Open collector (see user manual for additional interface information) |
| SNMP Interface | Allows full control and monitoring interface over network connection. Compatible with HP Openview™, IBM Netview™, CA Unicenter TNG™, and other major software offerings. |
|---|---|
| Battery Bus Voltage | 48 V or 72 V |