Ideal power protection for large diamond intersections
Voltage | 75 VAC to 155 VAC (before going to batteries) |
---|---|
Frequency | 45 Hz to 65 Hz |
Voltage | 120 VAC ±3% |
---|---|
Frequency | 50 Hz or 60 Hz |
Current | 16.7 A |
Rating | 2000 VA / 1400 W |
Crest Factor Ratio | 50% load up to 4.8:1, 75% load up to 3.2:1, 100% load up to 2.4:1 |
THD | 4.00% maximum |
Dynamic Response | ±4% for 100% step load change 0.5 ms recovery time |
Overload | 110% for 10 sec; 200% for 50 ms |
UPS Protection | Input and output short circuit, Input and output overload, Excessive battery discharge |
Temperature | -40°C to +74°C (-40°F to +165°F) |
---|---|
Humidity | 0% to 95% non-condensing |
Altitude | Sea level to 10,000 ft |
Input | Hardwired to bypass box |
---|---|
Outputs | Hardwired to bypass box, with single 15 Amp receptacle |
Dimensions H x W x D (in) |
3.5 x 19.0 x 10.0 (2U) |
Weight (lb) | 13 |
Cooling | Low velocity, Forced air |
Standard Features | Power factor corrected input, Fully regenerative, True on-line continuous power, Low distortion sine wave output, Designed for non-linear loads, Extended brownout protection, EIA/RS232 data interface, 96 VDC battery system |
---|---|
Certifications | IEEE 587/ANSI C62.4, IEC 555 @ 120 VA, NEMA |
Typical Recharge Time (to 85% Capacity @ 100% Load) |
48-72 hrs (more time required with extended battery option) |
Switches / Control Panel | System power, Cold start, Test, Alarm silence, Four line LCD display panel |
---|---|
Audible Alarms | Utility interrupt, Inverter failure, Overload, Low battery, Self test |
Intelligent Computer Interfaces | Serial interface for EIA 232, 1 each DB9-F (RS232 and signal interface pins) and 1 each USB, Full interactive remote computer monitoring and control of most features including load control (requires optional monitoring software), NTCIP and TCP/IP ready |
Contact Closures | "D" connector, Open collector (see user manual for additional interface information) |
SNMP Interface | Allows full control and monitoring interface over network connection. Compatible with HP Openview™, IBM Netview™, CA Unicenter TNG™, and other major software offerings. |
---|---|
Battery Bus Voltage | 96 V |