Voltage Ranges |
|
|
120 VAC +12%, -25% (without battery discharge) |
| |
Frequency |
|
|
48 to 62 Hz |
 |
|
|
| |
Voltage |
|
|
120 VAC ±3% |
| |
Frequency |
|
|
50 or 60 Hz |
| |
Rating |
|
|
SP1250U-MPL - 1,250 VA/875 Watts, SP1500U-MPL - 1,500 VA/1050 Watts,
SP2000U-MPL - 2,000 VA/1400 Watts & SP2400U-MPL - 2400VA/1680 Watts |
| |
Crest Factor Ratio (Non-linear Load and < 5%
THD) Typical |
|
|
| @50% Load |
 |
Up to 4.8:1 |
| @75% Load |
 |
Up to 3.2:1 |
| @100% Load |
 |
Up to 2.4:1 |
|
| |
Total Harmonic Distortion (THD) |
|
|
4.0% Max. |
| |
Dynamic Response |
|
|
±4% for 100% Step Load Change 0.5 ms Recovery
Time |
| |
Overload |
|
|
110% for 10 min; 200% for .05 sec |
| |
Efficiency @100% Load |
|
|
90% (Normal Mode) |
| |
UPS Protection |
|
|
Input and Output Short Circuit; Input and Output
Overload; Excessive Battery Discharge |
 |
|
|
| |
Operating Temperature |
|
|
0°C to +60°C (32°F to+122°F) |
| |
Humidity |
|
|
0% to 95% Non-condensing |
| |
Altitude |
|
|
Sea Level to 10,000 ft (some derating of temp.
w/altitude > 6,000 ft) |
| |
Noise Level |
|
|
46 dBA at 5 ft |
 |
|
|
| |
Input Connectors |
|
|
L5-30P Inlet Connector |
| |
Outputs(Standard) |
|
|
Eight NEMA 5-15R Receptacles |
| |
Cabinet |
|
|
NEMA, 332 or CBO-123 Cabinet Style Configurations Available;
NEMA 3R Type II and Type III Optional |
 |
|
|
| |
Consult Factory for other Custom options |
|
|
|
 |
|
|
| |
Standard Features |
|
|
Power Factor Corrected Input; Fully Regenerative;
True On-Line Continuous Power; Low Distortion Sinewave Output;
Designed for Non-linear Loads; Extended Brownout Protection;
EIA/RS232 Data Interface |
| |
Specifications |
|
|
Meets FCC Class A, IEEE 587/ANSI C62.4, IEC 555@
120 VAC and NEMA Stds |
| |
MTBF |
|
|
Inverter: > 100,000 hrs System w/Bypass: 150,000
hrs Calculated from Component Spec |
| |
Typical Recharge Time
85% Capacity @100% Load |
|
|
48-72 hrs (more time required with extended battery
option), Less than 20 hrs with optional Fast Battery Charger
|
 |
|
|
| |
Ramping LEDs Single LEDs |
|
|
Battery Level; Load Level AC In; Inverter On;
Low Battery and Summary Alarm; Alarm Silence |
| |
Control Panel |
|
|
Power On; Cold Start; Test; Alarm Silence; Event
Counter (w/Reset); Hour Meter; Battery Disconnect |
| |
Audible Alarms |
|
|
Utility Interrupt; Inverter Failure; Overload;
Low Battery; Self Test |
| |
TCP/IP Interface standard via
RJ45 |
|
|
Full Interactive Remote Computer Monitoring and
Control of Most Features Including Load Control; NTCIP and TCP/IP Ready |
| |
Contact Closures On Battery, ("D" connector)
|
|
|
Open Collector for Remote Annunciation of Power
Up, Power Down, Low Battery and Alarms |
| |
Specifications subject to change without prior
notice.
|
|
|
|
| |
 |
 |