Voltage Ranges |
|
|
208 - 240 VAC +10%, -20% Optional 120 VAC (Contact
Sales) |
| |
Frequency |
|
|
40 / 70 Hz |
 |
|
|
| |
Voltage |
|
|
120/208/220/230/240 VAC ±3% |
| |
Frequency |
|
|
50/60 Hz Selectable on front panel |
| |
Crest Factor Ratio |
|
|
5:1 (Peak to RMS Current) Handling |
| |
Total Harmonic Distortion (THD) |
|
|
2% Max. (Linear) |
| |
Overload (Temp. Dependent) |
|
|
120% for 20 minutes; 130% for 3.5 minutes |
| |
Efficiency @100% Load |
|
|
90-92% |
 |
|
|
| |
Operating Temperature |
|
|
-10°C to +40°C(14°F to+104°F) |
| |
Humidity |
|
|
0% to 95% Non-condensing |
| |
Altitude |
|
|
Sea Level to 10,000 ft (some derating of temp.
w/altitude > 7,000 ft) |
| |
Noise Level |
|
|
40 to 50 dBA at 3 ft |
 |
|
|
| |
Input |
|
|
Standard, Hard wired to terminal block, other options available |
| |
Outputs |
|
|
Standard, Hard wired to terminal block, other options available |
 |
|
|
| |
Redundant Parallel Architecture Option
Relay Card Option
SNMP Adapter Card
Emergency Power Off Connection (EPO)
Floor Bracket Kit
120VAC Input Voltage
L6-30P Input Line Cord, Models
Power Distribution Units (PDU)
Mobile Hand Cart, Models
External / Extended Run-time Battery Cabinets
Contact Factory for Other Custom Options |
|
|
|
 |
|
|
| |
Standard Features |
|
|
Power Factor Corrected Input; Fully Regenerative;
Low Distortion Sinewave Output Inverter Powers Load Continuously;
Designed for Non-linear Loads; Extended Brownout Protection;
Automatic Bypass; RS232 Data Interface |
| |
Specifications |
|
|
IEC 950; EN50091-01; EN 60950; IEEE 587/ANSI C62.41;
EN 50091-2; CE; UL 1778; CUL |
| |
MTBF |
|
|
In Excess of 100,000 hrs |
| |
Typical Recharge Time
85% Capacity @100% Load |
|
|
1.5 to 3hrs |
 |
|
|
| |
Single LED tLCD Screen |
|
|
Operation and Alarm t2 x 16 Characters |
| |
Front Panel Controls |
|
|
Power On; Cold Start; Alarm Silence; Test; Frequency
Select; Voltage Select |
| |
Audible Alarms |
|
|
Utility Interrupt; Inverter Failure; Overload;
Low Battery; Self Test |
| |
RS-232 Data Interface (DB-9) |
|
|
Full Interactive Remote Computer Monitoring and
Control of Most Features (requires optional monitoring software) |
| |
Relay Interface Card |
|
|
Potential Free Relay Contacts |
| |
Optional SNMP Interface |
|
|
Allows Full Control and Over Network Connection.
Compatible with HP Openview™, Netview™, Systems
Enhancement Corp. and Other Major Software. |
| |
Manual Bypass Switch |
|
|
This System can be Bypassed Manually for Testing
& Maintenance without Interruption of the Power supplied
to the Load. |
| |
Specifications subject to change without prior
notice. |
|
|
|
| S603* |
6,000 |
4,800 |
8 / 18 |
295 |
26.8 x 12.3 x 28.7 |
|
 |
 |