Larger VA rated products that also feature all-digital On-Line Double Conversion Technology. Designed to provide maximum performance and reliability with Power Factor Correction. Fully isolated output, and a wide range of input and output voltage and frequency selection options are also available. Ideally suited for server farms, telecommunication applications and many other mission-critical applications where reliability is a must! Available in Tower configuration. RATINGS: 6 kVA; input voltages of 208 and 240Vac are standard and output voltages of 120/208/220/230/240 VAC; 50/60 Hz. UL listed.

• True On-line Double Conversion
• Supports Redundant Parallel Architecture (RPA)
• Symmetrical or N+1 Capability
• Protects all connected equipment
• Superior Battery Management
• No interrupted procedures
• Enhanced patient security
• No invalid test result
• No revenue disruption
• Manual maintenance bypass switch

DIAGRAMS: Front and Rear Panel Operations Indicators
WARRANTY | PRODUCT MANUALS | PRODUCT BROCHURE

   
 
  ELECTRICAL    
  INPUT    
  Voltage Ranges     208 - 240 VAC +10%, -20% Optional 120 VAC (Contact Sales)
  Frequency     40 / 70 Hz
  OUTPUT    
  Voltage     120/208/220/230/240 VAC ±3%
  Frequency     50/60 Hz Selectable on front panel
  Crest Factor Ratio     5:1 (Peak to RMS Current) Handling
  Total Harmonic Distortion (THD)     2% Max. (Linear)
  Overload (Temp. Dependent)     120% for 20 minutes; 130% for 3.5 minutes
  Efficiency @100% Load     90-92%
  ENVIRONMENTAL    
 

Operating Temperature

    -10°C to +40°C(14°F to+104°F)
  Humidity     0% to 95% Non-condensing
  Altitude     Sea Level to 10,000 ft (some derating of temp. w/altitude > 7,000 ft)
  Noise Level     40 to 50 dBA at 3 ft
  MECHANICAL    
  Input     Standard, Hard wired to terminal block, other options available
  Outputs     Standard, Hard wired to terminal block, other options available
  AVAILABLE OPTIONS    
  Redundant Parallel Architecture Option
Relay Card Option
SNMP Adapter Card
Emergency Power Off Connection (EPO)
Floor Bracket Kit
120VAC Input Voltage
L6-30P Input Line Cord, Models
Power Distribution Units (PDU)
Mobile Hand Cart, Models
External / Extended Run-time Battery Cabinets
Contact Factory for Other Custom Options
     
  DESIGN    
  Standard Features     Power Factor Corrected Input; Fully Regenerative; Low Distortion Sinewave Output Inverter Powers Load Continuously; Designed for Non-linear Loads; Extended Brownout Protection; Automatic Bypass; RS232 Data Interface
  Specifications     IEC 950; EN50091-01; EN 60950; IEEE 587/ANSI C62.41; EN 50091-2; CE; UL 1778; CUL
  MTBF     In Excess of 100,000 hrs
  Typical Recharge Time
85% Capacity @100% Load
    1.5 to 3hrs
  CONTROL AND INDICATORS    
  Single LED tLCD Screen     Operation and Alarm t2 x 16 Characters
  Front Panel Controls     Power On; Cold Start; Alarm Silence; Test; Frequency Select; Voltage Select
  Audible Alarms     Utility Interrupt; Inverter Failure; Overload; Low Battery; Self Test
  RS-232 Data Interface (DB-9)     Full Interactive Remote Computer Monitoring and Control of Most Features (requires optional monitoring software)
  Relay Interface Card     Potential Free Relay Contacts
  Optional SNMP Interface     Allows Full Control and Over Network Connection. Compatible with HP Openview™, Netview™, Systems Enhancement Corp. and Other Major Software.
  Manual Bypass Switch     This System can be Bypassed Manually for Testing & Maintenance without Interruption of the Power supplied to the Load.
 

Specifications subject to change without prior notice.

     
Model
VA
Watts
Backup Time
100% / 50%
Load
Unit
Weight (lbs)
Dimensions
H x W x D
(inches)
S603*
6,000
4,800
8 / 18
295
26.8 x 12.3 x 28.7
 

150 East Huntington Drive. | Monrovia,CA 91016 | Tel:800-442-5279 or 626-359-4486 | Fax:626-305-0254