 |
|
|
 |
|
|
| |
Voltage Ranges |
|
|
120 VAC +12%, -25% (without battery discharge) |
| |
Frequency |
|
|
45 to 65 Hz |
| |
Current |
|
|
See Table Below, Power Factor Corrected per IEC
555 @ 120 VAC |
 |
|
|
| |
Voltage |
|
|
120 VAC ±3% |
| |
Frequency |
|
|
Software Selectable to Sync with Input Utility
or Run at Crystal Controlled 50/60 Hz ±1 Hz |
| |
Current |
|
|
See Table Below |
| |
Crest Factor Ratio (Non-linear Load and < 5%
THD) Typical |
|
|
| @50% Load |
 |
Up to 4.8:1 |
| @75% Load |
 |
Up to 3.2:1 |
| @100% Load |
 |
Up to 2.4:1 |
|
| |
Total Harmonic Distortion (THD) |
|
|
3% Max. (Linear)
5% Max. (Non-linear) |
| |
Dynamic Response |
|
|
±4% for 100% Step Load Change 0.5 ms Recovery
Time |
| |
Overload |
|
|
110% for 10 min; 200% for .05 sec |
| |
Efficiency @100% Load |
|
|
88% |
| |
UPS Protection |
|
|
Input and Output Short Circuit; Input and Output
Overload; Excessive Battery Discharge |
 |
|
|
| |
Operating Temperatures: |
|
|
± 0°C to +50°C (+32°F
to +122°F) |
| |
Humidity |
|
|
0% to 95% Non-condensing |
| |
Altitude |
|
|
Sea Level to 10,000 ft (some derating of temp.
w/altitude) |
| |
Noise Level |
|
|
39 to 42 dBA at 5 ft |
 |
|
|
| |
Input Connectors |
|
|
|
| |
2,000 . 2,400VA |
|
|
NEMA 5-20P Plug w/6 ft Cord |
| |
1,000/1,250/1,500 VA |
|
|
NEMA 5-15P Plug w/6 ft Cord |
| |
Outputs(Standard) |
|
|
(1) Duplex hospital grade receptacle 5-15R, 1K-1.5K
- 5-20R, 2K-2.4K |
| |
|
|
|
|
 |
|
|
| |
Hardwire Input/output; Input Circuit Breaker;
Emergency Power Off Connection; Input Air Filter, Slide Rail
Kit; Contact Factory for Other Custom Options |
|
|
|
 |
|
|
| |
Standard Features |
|
|
Power Factor Corrected Input; Fully Regenerative;
True On-Line; Low Distortion Sinewave Output; Inverter Powers
Load Continuously; Designed for Non-linear Extended Brownout
Protection; Continuous Operation on -25% to +12% Utility w/o
Draining Batteries; Automatic Bypass; RS232 Data Interface;
AC Output - 2 Channel Load Control; Rear Mounted Ground Stud |
| |
Specifications |
|
|
UL-60601-1; UL-1778; FCC Class A; IEEE 587/ANSI
C62.41; IEC 555@120 VAC |
| |
MTBF |
|
|
In Excess of 100,000 hrs |
| |
Typical Recharge Time
85% Capacity @100% Load |
|
|
8 hrs (more time required with extended battery
option) |
 |
|
|
| |
Sequenced LEDs Single LEDs |
|
|
Battery Level; Load Level AC In; Inverter On;
Load On; Summary Alarm; Alarm Silence |
| |
Front Panel Controls |
|
|
Power On; Cold Start; Alarm Silence; Test; Load
I On-Off; Load II On-Off Controls |
| |
Audible Alarms |
|
|
Utility Interrupt; Inverter Failure; Overload;
Low Battery; Self Test |
| |
RS-232 Data Interface (DB-9) |
|
|
Full Interactive Remote Computer Monitoring and
Control of Most Features, Including Load Control (requires optional
monitoring software). Compatible with: Systems Enhancement™
UPS Control Software. |
| |
Contact Closure (DB-9) |
|
|
Open Collector; Optional Dry Contact |
| |
Optional SNMP Interface |
|
|
Allows Full Control and Monitoring Interface over
Network Connection. Compatible with HP Openview™, IBM
Netview™, CA Unicenter TNG™, and other major software
offerings. |
| |
Specifications subject to change without prior
notice. |
|
|
|
| S1500-601 |
1,500 |
1,050 |
10.7 |
12.5 |
5 / 17 |
80 |
14.1 x 6.9 x 21 |
|
 |
 |