Voltage Ranges |
|
|
120 VAC +12%, -25% (without battery discharge) |
| |
Frequency |
|
|
45 to 65 Hz |
| |
Current |
|
|
See Table Below, Power Factor Corrected per IEC
555 @ 120 VAC |
 |
|
|
| |
Voltage |
|
|
120 VAC ±3% |
| |
Frequency |
|
|
Software Selectable to Sync with Input Utility
or Run at Crystal Controlled 50/60 Hz ±1 Hz |
| |
Current |
|
|
See Table Below |
| |
Crest Factor Ratio (Non-linear Load and <5%
THD) Typical |
|
|
| @50% Load |
 |
Up to 4.8:1 |
| @75% Load |
 |
Up to 3.2:1 |
| @100% Load |
 |
Up to 2.4:1 |
|
| |
Total Harmonic Distortion (THD) |
|
|
3% Max. (Linear)
5% Max. (Non-linear) |
| |
Dynamic Response |
|
|
±4% for 100% Step Load Change 0.5 ms Recovery
Time |
| |
Overload |
|
|
110% for 10 min; 200% for .05 sec |
| |
Efficiency @100% Load |
|
|
90% (Normal Mode) |
| |
UPS Protection |
|
|
Input and Output Short Circuit; Input and Output
Overload; Excessive Battery Discharge |
 |
|
|
| |
Operating Temperatures:
Standard Models
HT Models |
|
|
0°C to +40°C (+32°F to +104°F)
0°C to +60°C (+32oF to +140°F)
|
| |
Humidity |
|
|
0% to 95% Non-condensing |
| |
Altitude |
|
|
Sea Level to 10,000 ft (some derating of temp.
w/altitude) |
| |
Noise Level |
|
|
46 dBA at 5 ft |
 |
|
|
| |
Input Connectors |
|
|
|
| |
1,250-1,500VA |
|
|
NEMA 5-15P Plug w/6 ft Cord |
| |
2,000 VA |
|
|
NEMA 5-20P Plug w/6 ft Cord |
| |
2,400 VA |
|
|
NEMA L5-30 TL w/6 Ft Cord |
| |
Outputs(Standard) |
|
|
6 - NEMA 5-15R |
| |
|
|
|
|
 |
|
|
| |
Hardwire Input/output; Input Circuit Breaker;
Emergency Power Off Connection; Input Air Filter, Slide Rail
Kit; Contact Factory for Other Custom Options |
|
|
|
 |
|
|
| |
Standard Features |
|
|
Power Factor Corrected Input; Fully Regenerative;
True On-Line;
Low Distortion Sinewave Output; Inverter Powers Load Continuously;
Designed for Non-linear Loads; Extended Brownout Protection;
Continuous Operation on -25% to +12% Utility w/o Draining Batteries;
Automatic Bypass; RS232 Data Interface; AC Output - 2 Channel
Load Control; Rear Mounted Ground Stud |
| |
Specifications |
|
|
UL 1778; CUL; FCC Class A; IEEE 587/ANSI C62.41;
IEC 555 @120 VAC |
| |
MTBF |
|
|
In Excess of 100,000 hrs |
| |
Typical Recharge Time
85% Capacity @100% Load |
|
|
8 hrs (more time required with extended battery
option) |
 |
|
|
| |
Sequenced LEDs Single LEDs |
|
|
Battery Level; Load Level AC In; Inverter On;
Load On; Summary Alarm; Alarm Silence |
| |
Front Panel Controls |
|
|
Power On; Load I On/Off; Cold Start; Load II On/Off;
Alarm Silence; Test |
| |
Audible Alarms |
|
|
Utility Interrupt; Inverter Failure; Overload;
Low Battery; Self Test |
| |
RS-232 Data Interface (DB-9) |
|
|
Full Interactive Remote Computer Monitoring and
Control of Most Features, Including Load Control (requires optional
monitoring software). Compatible with: Systems Enhancement™
UPS Control Software. |
| |
Contact Closure (DB-9) |
|
|
Open Collector |
| |
Optional SNMP Interface |
|
|
Allows Full Control and Monitoring over Network
Connection. Compatible with HP OpenView™, IBM Netview™,
CA Unicenter TNG™, Systems EnhancementCorp. and Other
Major Software. |
| |
Specifications subject to change without prior
notice. |
|
|
|
DT1250R |
DT1250T |
1,250 |
875 |
8.8 |
10.4 |
7 / 21 |
42 |
3.5 x 19.0 x 17.0 (2U) |
9.3 x 7.0 x 16.25 |
DT1500R |
DT1500T |
1,500 |
1,050 |
10.7 |
12.5 |
5 / 17 |
42 |
3.5 x 19.0 x 17.0 (2U) |
9.3 x 7.0 x 16.25 |
DT2000R |
DT2000T |
2,000 |
1,400 |
14.3 |
16.7 |
5 / 18 |
55 |
5.25 x 19.0 x 23 (2U) |
9.3 x 7.0 x 20.25 |
DT2400R |
DT2400T |
2,400 |
1,618 |
18.3 |
20.0 |
4.5 / 14 |
55 |
5.25 x 19.0 x 23 (3U) |
9.3 x 7.0 x 20.25 |
|
 |
 |