Voltage Ranges |
|
|
120 VAC +10%, -20% (Other input voltages available) |
| |
Frequency |
|
|
45 to 65 Hz |
| |
Current |
|
|
See Table Below |
 |
|
|
| |
Voltage |
|
|
120 VAC ±3% (Other output voltages available) |
| |
Frequency |
|
|
Software Selectable to Sync with Input Utility
or Run at Crystal Controlled 50 or 60 Hz ±1 Hz |
| |
Current |
|
|
See Table Below |
| |
Crest Factor Ratio (Non-linear Load and < 5%
THD) Typical |
|
|
| @50% Load |
 |
Up to 4.8:1 |
| @75% Load |
 |
Up to 3.2:1 |
| @100% Load |
 |
Up to 2.4:1 |
|
| |
Total Harmonic Distortion (THD) |
|
|
3% Max. (Linear)
5% Max. (Non-linear) |
| |
Dynamic Response |
|
|
±4% for 100% Step Load Change 0.5 ms Recovery
Time |
| |
Overload |
|
|
110% for 10 min; 200% for .05 sec |
| |
Efficiency @100% Load |
|
|
88% (90% Typical) |
| |
UPS Protection |
|
|
Input and Output Short Circuit;Input and Output
Overload; Excessive Battery Discharge |
 |
|
|
| |
Operating Temperatures:
Standard Models |
|
|
0°C to +40°C (+32°F to +104°F) |
| |
Humidity |
|
|
0% to 95% Non-condensing |
| |
Altitude |
|
|
Sea Level to 10,000 ft (some derating of temp.
w/altitude) |
| |
Noise Level |
|
|
39 to 42 dBA at 5 ft |
 |
|
|
| |
Input Connectors |
|
|
|
| |
1,250/1,500 VA |
|
|
NEMA 5-15P Plug w/6 ft Cord |
| |
2,000/2,400VA |
|
|
NEMA 5-20P Plug w/6 ft Cord |
| |
Outputs(Standard) |
|
|
3 – NEMA Duplex Receptacles 5-15R, 1.25K-1.5K,
5-20R, 2K-2.4K |
| |
|
|
|
|
 |
|
|
| |
Contact Factory for Other Custom Options
Specifications subject to change without prior notice. |
|
|
|
 |
|
|
| |
Standard Features |
|
|
Power Factor Corrected Input; Fully Regenerative;
True On-Line; Low Distortion Sinewave Output; Inverter Powers
Load Continuously; Designed for Non-linear Loads; Extended Brownout
Protection; Continuous Operation on -25% to +12% Utility w/o
Draining Batteries; Automatic Bypass; RS232 Data Interface;
AC Output - 2 Channel Load Control; Rear Mounted Ground Stud |
| |
Specifications |
|
|
UL 1778; CUL; FCC Class A; IEEE 587 /
ANSI C62.41;IEC 555 @120VAC |
| |
MTBF |
|
|
In Excess of 100,000 hrs |
| |
Typical Recharge Time
85% Capacity @100% Load |
|
|
5 hrs |
 |
|
|
| |
Sequenced LEDs Single LEDs |
|
|
Battery Level, Load Level AC In, Inverter On, Load
On, Summary Alarm, Alarm Silence |
| |
Front Panel Controls |
|
|
Power On; Cold Start; Alarm Silence; Test; Load
I On-Off; Load II On-Off |
| |
Audible Alarms |
|
|
Utility Interrupt; Inverter Failure; Overload;
Low Battery; Self Test |
| |
RS-232 Data Interface (DB-9) |
|
|
Full Interactive Remote Computer Monitoring and
Control of Most Features,
Including Load Control (requires optional monitoring software).
Compatible with RUPS tm and RUPS II™ and other major UPS software
products. |
| |
Contact Closure (DB-9) |
|
|
Open Collector or Optional Dry Contact Module
|
| |
Optional SNMP Interface |
|
|
Allows Full Control and Monitoring over a network
connection. Compatible with HP Openview™, IBM Netview™,
CA Unicenter TNG™ and other major UPS software products. |
| |
Specifications subject to change without prior notice. |
|
|
|
| CT1250R |
1,250 |
8.8 |
10.4 |
7 / 21 |
42 / 79 |
5.25 x 19.0 x 17.0 (3U) |
5.25 x 19.0 x 23.0 (3U) |
| CT1500R |
1,500 |
10.7 |
12.5 |
8 / 20 |
42 / 79 |
5.25 x 19.0 x 17.0 (3U) |
5.25 x 19.0 x 23.0 (3U) |
| CT2000R |
2,000 |
14.3 |
16.7 |
6 / 22 |
55 / 92 |
5.25 x 19.0 x 17.0 (3U) |
5.25 x 19.0 x 23.0 (3U) |
| CT2400R |
2,400 |
18.3 |
20.0 |
4 / 14 |
55 / 95 |
5.25 x 19.0 x 17.0 (3U) |
5.25 x 19.0 x 23.0 (3U) |
|
 |
 |