Monrovia, CA: 800-442-5279 - 626-359-4486 Richmond, VA: 888-442-5279
 

 

 

 

All Clary CMN Series systems are custom manufactured devices that support Clary's POWER Channel technology, consult factory for availability.

Unlike commercial standby and hybrid UPS products, Clary's CMN Series products are designed and built to rugged specifications. All systems are digitally microprocessor controlled to provide clean, regulated power under all tactical conditions. All CMN Series systems are Power Factor Corrected (PFC) in real-time to ensure the highest possible efficiency. Full RS232 and SNMP interactive communications capability assures support of all types of command and control applications. 1,250/1,500/2,000/2,400 and 4000VA; 120 through 240 VAC input 45 to 65 Hz, 120 through 240VAC output; 50 or 60 Hz. UL listed.

Rack Mount
ET Models
Rack Mount
ST Models
Rating Watts
       
CMN1250ET CMN1250ST 1,250 VA 875
CMN1500ET CMN1500ST 1,500 VA 1,050
CMN2000ET CMN2000ST 2000 VA 1,400
CMN2400ET CMN2400ST 2400 VA 1,680
CMN3000ET CMN3000ST 3000VA 2,100
N/A CMN4000ST 4000 VA 2,800

• Small size - 5.25” - 3U Rack Space
• Power Factor Corrected to near unity
• Rackmount version fits into standard 19” Rack
• Outputs can be controlled remotely or from front panel (Optional)
• Software selectable configuration (output frequency, voltage, alarms, auto turn-off, etc.)
• Automatic bypass & battery test
• Unit can be started with out AC present (Cold Start)
• Many options available for custom configurations
• Transformer Isolation included

WARRANTY | BROCHURES | MANUALS

   
 
  ELECTRICAL    
  INPUT    
  Voltage Ranges     120 VAC +12%, -25% (without battery discharge)
  Frequency     45 to 65 Hz
  Current     See Table Below, Power Factor Corrected per IEC 555 @ 120 VAC
  OUTPUT    
  Voltage     120 VAC ±3%
  Frequency     Software Selectable to Sync with Input Utility or Run at Crystal Controlled 50/60 Hz ±1 Hz
  Current     See Table Below
  Crest Factor Ratio (Non-linear Load and < 5% THD) Typical    
@50% Load Up to 4.8:1
@75% Load Up to 3.2:1
@100% Load Up to 2.4:1
  Total Harmonic Distortion (THD)     3% Max. (Linear)
5% Max. (Non-linear)
  Dynamic Response     ±4% for 100% Step Load Change 0.5 ms Recovery Time
  Overload     110% for 10 min; 200% for .05 sec
  Efficiency @100% Load     90% (Normal Mode)
  UPS Protection     Input and Output Short Circuit; Input and Output Overload; Excessive Battery Discharge
  ENVIRONMENTAL    
 

Operating Temperatures:
ST Models
ET Models

   
0°C to +50°C (+32°F to +122°F)
-40°C to +74°C (-40°C to +167°C)
  Humidity     0% to 95% Non-condensing
  Altitude     Sea Level to 10,000 ft (some derating of temp. w/altitude)
  Noise Level     46 dBA at 5 ft
  MECHANICAL    
  Input Connectors     Consult Factory
  1,250-1500VA      
  2000 - 2400VA      
  3000 - 4000VA      
  Outputs(Standard)     Consult Factory
  1250 - 1500VA      
  2000 - 4000VA      
  CUSTOM OPTIONS    
  Many Exist, Contact Factory for Other Standard or Custom Options.      
  DESIGN    
  Standard Features     Power Factor Corrected Input; Fully Regenerative; True On-Line; Low Distortion Sinewave Output; Inverter Powers Load Continuously; Designed for Non-linear Loads; Extended Brownout Protection; Continuous Operation on -25% to +12% Utility w/o Draining Batteries; Automatic Bypass; RS232 Data Interface; AC Output - 8 Channel Load Control; Rear Mounted Ground Stud
  Specifications     UL 1778; CUL; FCC Class A; IEEE 587/ANSI C62.41; IEC 555 @120 VAC
  MTBF     In Excess of 100,000 hrs
  Typical Recharge Time
85% Capacity @100% Load
    8 hrs (more time required with extended battery option)
  CONTROL AND INDICATORS    
  Sequenced LEDs Single LEDs     Battery Level; Load Level AC In; Inverter On; Load On; Summary Alarm; Alarm Silence
  Front Panel Controls     Power On; Load I On/Off; Cold Start; Load II On/Off; Alarm Silence; Test
  Audible Alarms     Utility Interrupt; Inverter Failure; Overload; Low Battery; Self Test
  RS-232 Data Interface (DB-9)     Full Interactive Remote Computer Monitoring and Control of Most Features, Including Load Control (requires optional monitoring software). Compatible with: Systems Enhancement™ UPS Control Software.
  Contact Closure (DB-9)     Open Collector
  Optional SNMP Interface     Allows Full Control and Monitoring over Network Connection. Compatible with HP OpenView™, IBM Netview™, CA Unicenter TNG™, Systems EnhancementCorp. and Other Major Software.
 

Specifications subject to change without prior notice.

     
         
Model
Rackmount
Model
Tower
VA
Watts
Input
Current
(A)
Output
Current
(A)
Backup Time
100% / 50%
Load
Unit
Weight
(lbs)
Rack
H x W x D
(inches)
Tower
H x W x D
(inches)
CMN1250 ET/ST
N/A
1,250
875
8.8
10.4
7 / 21 Min.
80
5.25 x 19.0 x 23.0(3U)
N/A
CMN1500 ET/ST
N/A
1,500
1,050
10.7
12.5
5 / 17 Min.
80
5.25 x 19.0 x 23.0(3U)
N/A
CMN2000 ET/ST
N/A
2,000
1,400
14.3
16.7
5 / 18 Min.
80
5.25 x 19.0 x 23.0(3U)
N/A
CMN2400 ET/ST
N/A
2,400
1,680
18.3
20.0
4 / 12 Min.
83.5
5.25 x 19.0 x 23.0(3U)
N/A
CMN3000 ET/ST
N/A
3,000
2,100
28
25
Battery Option Dependent
90
5.25 x 19.0 x 23.0(3U)
N/A
CMN4000 ET/ST
N/A
4,000
2,800
42
34
Battery Option Dependent
90
5.25 x 19.0 x 23.0(3U)
N/A
 